Project Description
- Certificate: UL Listed / FM Approved
- Standard: UL 199, NFPA 13
- Feature: K5.6 (K80), SR, HSW
- W. pressure: 250 / 175 psi
- T. pressure: 500 psi, factory hydrostatic test
- O. pressure: Min 7 psi
- Surface: Rough brass / chrome plated / white painted, etc.
K5.6 standard response horizontal sidewall sprinkler is usually used in light and ordinary hazard occupancies. The deflector discharges most of the water in a horizontal plane onto adjacent walls and the protected area.
Available size (Source 1 with UL/FM)
Type Temperature rating Working pressure (psi) Ref. No. Horizontal sidewall 135°F (57°C) 250 S0401 (UL/FM) Horizontal sidewall 155°F (68°C) 250 S0402 (UL/FM) Horizontal sidewall 175°F (79°C) 250 S0403 (UL/FM) Horizontal sidewall 200°F (93°C) 250 S0404 (UL/FM) Horizontal sidewall 286°F (141°C) 250 S0405 (UL/FM) Horizontal sidewall 360°F (182°C) 250 S0406 (UL) Recessed horizontal sidewall 135°F (57°C) 250 S0407 (UL/FM) Recessed horizontal sidewall 155°F (68°C) 250 S0408 (UL/FM) Recessed horizontal sidewall 175°F (79°C) 250 S0409 (UL/FM) Recessed horizontal sidewall 200°F (93°C) 250 S0410 (UL/FM) Note:
1. As UL rule, it is used for ordinary and light hazard occupancies, and installed 4″ to 12″ below the ceiling.
2. For recessed sprinkler, it is assembled with a specified recessed escutcheon which provides adjustment up to 3/4″ (19.1 mm).Available size (Source 2 with UL/FM)
Type Temperature rating Working pressure (psi) Ref. No. Horizontal sidewall 135°F (57°C) 175 S0421 (UL/FM) Horizontal sidewall 155°F (68°C) 175 S0422 (UL/FM) Horizontal sidewall 175°F (79°C) 175 S0423 (UL/FM) Horizontal sidewall 200°F (93°C) 175 S0424 (UL/FM) Horizontal sidewall 286°F (141°C) 175 S0425 (UL/FM) Note: As UL rule, it is used for ordinary hazard occupancies, and installed 4″ to 12″ below the ceiling.